Moulded Case Circuit Breaker K. S. TERMINALS INC. 1 SPB-EMN Series Model IEC/EN 60947-2 Poles 3P Certification Electrical Specifiction Rated Frame Level Current Inm(A) 63 125 250 Rated Current(A) ln 16,20,25,32,40,50,63 16,20,25,32,40,50,63,70, 80,100,125 100,125,160,175,200,225,250 Rated Insulated Voltage Ui(AC V) 500 690 690 Rated Impulse Withstand Voltage Uimp(V) 6000 8000 8000 Rated Working Voltage Ue(AC V) 400/415V 400/415V 400/415V Rated Limited Short-circuit Breaking Capacity lcu(kA) BreakingType N N N 220/230V(kA) 25 28 43 380/415V(kA) 20 25 35 480/500V(kA) 10 15 15 660/690V(kA) 8 10 10 DC 250V 10 15 10 Rated Working Short-circuit Breaking Capacity Ics V %lcu 75 75 75 Insolation Insolation ■ Service Life (O-C) Mechanical Standard Value 10000 10000 8500 Electrical Standard Value 2000 2000 1500 Control And indication Control model Manual Direct (RHD) □ Extended (ERH) □ Electric (MOD) □ Shunt Release(SHT) □ Undervoltage Release(UVT) □ Auxiliary Contact(AUX) □ Alarm Contact(ALT) □ Connection And lnstallation protection degree Wiring ALL Side IP40 Wiring Terminal IP20 Wiring Assembly Front/Rear Front/Rear Front/Rear Plug-in Assembly □ □ □ Draw-out Assembly - - - Arcing Distance(mm) 0, 50 ■Standard Configuration SPB-EMN63A3Pxx 2P, 3P 3P SPB-EMN125A2P/3Pxx xx: Input rated current, for example, 50 amps, product part number SPB-EMN63A3P50 SPB-EMN250A3Pxx 15